WKSL 05/11 PG2
INSTALLATION INSTRUCTIONS
FOR WKSL SERIES COOLING UNITS
The BREEZAIRE WKSL Series cooling units are designed to, when installed in a properly
constructed enclosure, provide a constant, selectable temperature between 48°F and 6F while
reducing the excess relative humidity to the proper 50% to 75%. BREEZAIRE cooling units are
designed to lower the temperature, while removing only excessive moisture. In a properly
constructed enclosure this process can raise the relative humidity. The unit does not add moisture
to the enclosure. The unit does not include a heating system and will not warm the enclosure.
The WKSL Series is not intended to cool service cabinets, which are maintained at lower
temperatures and opened or entered frequently.
The WKSL Model has a digital electronic (Sentry III) thermostat that adds additional safety and
convenience features:
Large, easy to read, green LED display.
Accurate, easy to adjust (no tools needed), readable set points with continuous reading of
enclosure temperature or displaying of the set point when changing enclosure temperatures.
Power outage protection, which delays unit start up after power outages.
Blocked airflow protection, which shuts down unit and protects wine in case of high temperatures
caused by condenser blockage.
Controls temperature by enclosure intake air sensors or an optional bottle probe.
The WKSL Series cooling unit, is shipped as components, not a working cooling system. Only
after a qualified refrigeration installer has properly connected these components, pressured tested,
evacuated, charged with refrigerant and tested their installation, can the unit be considered a
cooling system. Proper installation is critical to the performance, reliability and longevity of the
system. For this reason, BREEZAIRE can only warrant the quality of the WKSL components. The
installation and proper operation must be warranted by the installer. Before installation, the
purchaser and installer should carefully read the enclosed Limited Warranty.
ENCLOSURE CONSTRUCTION GUIDELINES
To use the below SIZING GUIDE, the enclosure to be cooled must be built to the following
minimum specifications. If the enclosure cannot be built to these specifications, consult your
BREEZAIRE dealer for assistance in choosing the correct unit. BREEZAIRE units are not
warranted to cool a specific enclosure.
All walls, floors and ceilings should have a vapor barrier. This vapor barrier should be installed
on the warm side of the insulation. All interior walls and floors should be lined with a minimum of
R-11 insulation and exterior walls and ceiling insulation value should be a minimum of R-19.
There should be no glass doors and/or windows.
All joints, door frames, electrical outlets or switches and any pipes or vents which go through
the enclosure should be sealed to prevent air and moisture leakage into the room. Concrete, rock
and brick are not insulation or moisture barriers.
Doors into the enclosure should be of minimum size, insulated to R-11 and be tightly sealed
with a high quality weather stripping. Be sure to seal the bottom of the door and fill the gap
between the door's frame and wall before installing the cap molding.
Enclosure lighting should be of low wattage, with a timer to insure lights are not left on when
the enclosure is unoccupied. Recessed lighting should not be used as they will allow outside air to
enter the enclosure.